Fläkt Group: CFD-Driven Optimization of a High-Capacity Chilled Beam

Background

Walk into a comfortable office, hotel or hospital and there’s a whole system working quietly overhead to keep the air fresh and the temperature right. Fläkt Group builds those systems. The company makes HVAC and indoor climate systems that are used around the world, from air handling units to ventilation and cooling. Energy efficiency and healthy indoor environments are at the heart of what it does.

One product where Fläkt Group’s airflow know-how really counts is the active chilled beam. Picture a slim unit mounted in the ceiling. Fresh, cool air is pushed through a row of small nozzles inside it. Those fast jets pull warmer room air up and across a water-cooled coil, a bit like how a fast-moving stream drags the water around it along. The cooled room air then mixes with the fresh air and flows back down into the room.

Here’s the interesting part: most of the cooling comes from that room air being pulled over the coil, not from the fresh air itself. So the shape of the space inside the beam matters – a lot. A small tweak to the internal chamber can change how the jets behave, how much room air gets pulled in, and how evenly cool air spreads around the room.

Fläkt Group already uses simulation as a normal part of developing products. For this project, the team wanted to test some ideas for reshaping that internal chamber, and they wanted to do it on a computer first, using computational fluid dynamics (CFD), instead of going straight to building and testing prototypes.

 

The Challenge: Developing a High-Performance Chilled Beam

The big question was simple to ask and hard to answer: which chamber shape works best, and how do you find out without building a prototype for every idea?                         

High-capacity chilled beams have a tough job. They need to push a lot of cooling into a room while keeping the airflow steady and even. If the air inside the beam doesn’t flow evenly, some parts of the coil end up doing more work than others. That can mean less cooling, warm and cold patches in the room, or a draught that has people reaching for another layer of clothing.

The shape of the chamber affects pretty much everything that matters:

 

  • Where the jets go once the air leaves the nozzles.
  • How much room air gets pulled in for every litre of fresh air (called induction).
  • Pressure drop, which decides how hard the building’s fans have to work.
  • Comfort, meaning the air speed and temperature people actually feel.

 

The tricky bit is that these all affect each other. Improve one, and you might quietly make another one worse. A shape that spreads air nicely could change the temperature pattern in ways you’d never spot just by looking at a drawing.

The usual way to check is to build a prototype and test it in a climate lab. Lab testing is still essential, but it’s slow and expensive when you’ve got lots of ideas to try. Every version needs to be built, booked in, wired up with sensors and analysed. And even then, sensors only tell you what’s happening at the spots where they sit. They can’t show you why the air behaves the way it does inside a closed box.

So Fläkt Group needed a way to see inside the beam before building anything. That would let them rule out weaker ideas early and only take the most promising ones into the lab.

 

The Engineering Solution

The team built a virtual version of the whole test room and ran two chamber designs through it, Case A and Case B. Everything else was kept exactly the same, so any difference in the results came down to the shape alone.

Keeping it a fair fight

Instead of modelling just the beam on its own, they modelled the entire room. That way they could see how air leaving the beam actually moves through the space it’s supposed to cool. Both designs got identical conditions: 49 litres of fresh air per second, supplied at 15 °C. The main things they looked at were air speed and temperature around the room, with pressure drop used as a sanity check.

FlaktGroup chilled beam design outline

Design A and Design B side-by-side view (L-R)

 

Putting the detail where it counts

CFD splits a space into lots of tiny cells and works out how air moves through each one. More cells mean more detail, but also longer run times. So the team packed extra cells around the nozzles and the parts inside the beam, where the jets form and things change fastest. They also added fine layers next to walls and surfaces, where air behaves differently. Out on the room floor, where less is going on, they used bigger cells to keep things quick. Both designs used exactly the same approach.

 

FlaktGroup Mesh Preparation of chilled beam

Mesh preparation of the beam showing various quality of meshing

 

What the airflow looked like

The colour maps of air speed told a clear story. In Case A, the air spread out more inside the chamber. In Case B, it was channelled more tightly along the sides.

Flakt Group chilled beam velocity contours

Velocity contour comparison between design A and B (L-R)

 

The temperature maps added another layer. Case A had more patchy temperatures inside the chamber, while Case B was noticeably more even. In other words, changing the shape didn’t just change where the air went. It changed how the heat was spread too.

Flakt Group CFD results for temperature distribution of chilled beam design

Temperature distribution comparison of design A and B (L-R)

 

The numbers

With the same airflow and the same supply temperature, Case A pulled in almost twice as much room air as Case B, and it did so with practically the same pressure drop.

Result Case A Case B In plain terms
Induction ratio 8.94 4.69 Case A pulls in about 1.9 times more room air
Pressure drop 109.8Pa 109.0Pa Less than 1% apart, so no real extra fan energy either way
Room outlet temperature 19.34°C 20.37°C Air leaving the room is about 1°C warmer with Case B
Diffuser outlet temperature 15.51°C 15.50°C Basically the same air coming out of the beam
Coil temperature 15.57°C 15.60°C Basically the same conditions at the coil

 

Put together, the velocity maps, temperature maps, induction figures and checks gave the team a clear picture of how each design behaves, and why. That fed straight into their design discussions before anything went near the lab.

 

Benefits for HVAC Product Development

In short, CFD let Fläkt Group compare designs early, understand what was really going on inside the beam, and lean less on trial and error.

Smarter decisions, sooner

The team could put the two chamber designs side by side before building anything physical. Rather than making a prototype for every idea and waiting for lab results, they could sort the promising designs from the rest on screen. That moves the learning to the start of the project, which is exactly when changes are cheapest.

Seeing what sensors can’t

Lab sensors give you readings at a handful of points. CFD shows you the whole picture, inside the chamber and across the room. That made it much easier to explain why the two designs behaved differently. Case A spreads the air wider and pulls in far more room air. Case B keeps the flow along the sides and gives a more even temperature. You’d struggle to work that out from a drawing alone.

It also brought a real trade-off into the open. The design with the highest induction wasn’t the one with the most even internal temperature. Seeing both side by side gives the engineers solid facts to weigh cooling power against comfort, rather than relying on guesswork.

Less trial and error

Because the simulations explained the physics behind each design, Fläkt Group didn’t have to rely so heavily on building and testing to find out what works. Fewer guesswork prototypes means less material, fewer lab hours and quicker turnarounds. Physical testing still matters, but now it’s there to confirm a design the team already understands, not to discover how it behaves.

More performance, same energy

Both designs had almost exactly the same pressure drop, around 109Pa. So the study showed that reshaping the chamber can nearly double the amount of room air pulled in, without making the fans work any harder. For a company that cares about energy efficiency, that’s a handy benefit to have: you can tune cooling and comfort through smart internal design instead of just pushing more air.

A method they can reuse

Maybe the biggest win is the approach itself. Model the full room, keep the conditions identical, use the same mesh strategy, then compare speed, temperature, induction and pressure drop. Fläkt Group can now use that same process on future chilled beams and other airflow products.

Source: Fläkt Group presentation “CFD-Driven Optimization of High-Capacity Chilled Beam”, Meet the Experts 2026 series, Gothenburg

 